QUANTUM PLUS UPS SERIES
3/3 Uninterruptible Power Supplies
10kVA - 15kVA
• Online-Double conversion
• Output transfer time is 0ms
• PFC technology
• Full digital control (DSP)
• Output power factor 0.9
• Input current harmonic: ≤ 3%
• Eco Mode function
• Charging/Rectifier/Inverter/ fully digital control technology
• Optimization battery group, the quantity of battery: 10~30k (16/18/20 pcs optional) (20 pcs standard)
• Wide input voltage range: 208~478VAC
• Wide input frequency range: 40~70Hz
• Cold start
• Communication port: USB/RS232/RS485/parallel port/dry contact
• Options: SNMP card/relay card
• LCD / LED double display
• Intelligent charging management
• EPO function
• Common battery group
• The output can meet 100% unbalanced load
MODEL |
QUANTUM PLUS 310 |
QUANTUM PLUS 315 |
Capacity (kVA/kW) |
10kVA/9kW |
15kVA/13.5kW |
INPUT |
||
Nominal voltage |
380/400/415VAC, (3P+N+PE) |
|
Operating voltage range |
208 ~ 478VAC |
|
Operating frequency range |
45~55Hz at 50Hz / 54~66Hz at 60Hz (auto sensing) |
|
Power factor |
≥ 0.99 |
|
Bypass voltage range |
380VAC max. voltage: +25% (optional +10%, +15%, +20%) |
|
400VAC max. voltage: +20% (optional +10%, +15%) |
||
415VAC max. voltage: +15% (optional + 10%) |
||
Min. voltage: - 45% (optional -20%, -30%) |
||
Bypass frequency range |
Frequency synchronize tracing range: ±10% |
|
ECO mod |
Same as by-pass |
|
THDi |
≤ 3% (100% non-linear load) |
|
OUTPUT |
||
Output voltage |
380/400/415VAC (3P+N+PE) |
|
Power factor |
0.9 |
|
Voltage regulation |
± 1% |
|
Frequency Line mode |
± 1% / ± 2% / ± 4% / ± 5% / ± 10% of the rated frequency (optional) |
|
Bat. mode |
50/60 (± 0.1Hz) |
|
Crest factor |
3:1 |
|
THD |
≤ 2% with linear load |
|
≤ 5% with non-linear load |
||
Efficiency |
93.50% |
94.50% |
BATTERY |
||
Battery voltage |
Standard unit: ±120VDC (20pcs12V/9Ah); |
Standard unit: ±120VDC (2x20pcs12V/9Ah); |
(Optional) Long run unit: ±96V/±108V/±120Vdc (16/18/20pcs) |
(Optional) Long run unit: ±96V/±108V/±120Vdc (16/18/20pcs) |
|
Charge current |
Standard unit 1.35A, Long run unit: max current 10A |
Standard unit 2.7A, Long run unit: max current 10A |
SYSTEM FEATURES |
||
Transfer time |
Utility to battery: 0ms; Utility to by-pass: 0ms |
|
Overload |
Load ≤ 110%; last 60min, ≤ 125%: last 10min, ≤ %150: last 1min, ≥ %150 change to by-pass |
|
Short circuit |
Hold Whole System |
|
Communication |
USB, RS232, RS485, Parallel port, REPOport, Coupler dry contact, Intelligent slot, SNMP card (optional), Relay card (optional). |
|
ENVIRONMENTAL |
||
Operating temperature |
0 - 40°C |
|
Storage temperature |
−25 ~ 55°C (no battery) |
|
Humidity range |
0 - 95% (non-condensing) |
|
Altitude |
< 1500m. When > 1500m, lower the rated power for use |
|
Noise level |
< 55dB |
< 58dB |
PHYSICAL |
||
Dimensions HxWxD(mm) |
868x258x828 |
|
Net weight (kg) |
115/57 (with battery/without battery) |
170/63 (with battery/without battery) |
STANDARDS |
||
Safety |
IEC/EN62040-1, IEC/EN60950-1 |
|
EMC |
IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, |