DS POWER X UPS SERIES

3/3 Uninterruptible Power Supplies

100kVA - 400kVA

The new DX Power range UPS uses the latest DSP technology to be programmed to suit a wide variety of electrical environments without impending its performance. With the DS Power range, efficiency, reliability and functionality are enhanced to levels unattainable with the old analogue technology. This technology does not only create significant increase in MTBF, but the capability of DSP to accurately manipulate signals at very high speed permits all the UPS subsystems to be controlled with greatly increased precision.

• Transformerless UPS topology
• 3 Level rectifier and inverter
• High input power factor
• High efficiency up to 96.0%
• Cold start function
• Static and maintenance by-pass switch
• Output short circuit and overload protection
• External REPO switch input
• 512 events memory (512 events 45000 alarms)
• Clock and calender (battery supported)
• Automatic battery test,remaining battery time indicator
• Temperature compansated charge system (optional)
• 2 RS232 serial ports and 12 dry contact outputs
• 3 DSP controlled modular structure
• Optional SNMP and MODBUS adaptors
• Optional graphical panel
• Optional usb flash memory
• Full digital structure
• Small footprint
• Ecomode operation (optional)
• Fewer electronic components
• Output current limiting
• Advanced diagnostics for the input
• Selectable input/output voltage/frequency/range
• Split by-pass input (second input)
• Output DC leakage protection
• Separate DSP for inverter control
• Separate DSP for the PFC
• 3 level battery protection
• High charge current capacity
• Charge/discharge current indicator
• Advanced remote control features
• Manufactured according to EC Directive; EN62040
• 2 years warranty
• 10 years spare parts support

MODEL
DX3100
DX3120
DX3160
DX3200
DX3250
DX3300
DX3400
Rated Power
100
120
160
200
250
300
400
By-pass voltage
380/400 VAC 3 Phase + N, ± 10 (adjustable)
Frequency range
50Hz / 60Hz, ± 5%
OUTPUT
Voltage
380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency
50Hz / 60Hz
Frequency tolerance
Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Overload protection
at 100% - 125% load : 10 min. - at 125% - 150% load :1 min. - > at 150% load : by-pass
Current Crest Ratio
3:1
Effiency
up to 95.5%
up to 96%
BATTERY
Battery type
VRLA AGM / GEL / NiCd
Nominal voltage
± 360 VDC
Battery test
Standard every 72 hours (adjustable)
OPTIONS
Software
T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 10-50-100-200 clients
PHYSICS CHARACTERISTIC
Dimensions (mm) HxWxD 
1440x475x890
1900x880x775
1900x1250x775
ENVIRONMENT
Relative humidity
< 90% max. (non-condensing)
Acoustic noise
< 62 dBA
< 65 dBA
< 67 dBA